Product Introduction
The device features 35mm standard rail mounting with a remote RS-485 communication interface, meeting all
technical requirements for electricity meters specified in GB/T17215 and DL/T614. It utilizes DL/T645-2007
protocol compatibility with MODBUS-RTU to enable data exchange with host computers, facilitating energy
measurement, power consumption monitoring, data visualization, and remote transmission. Widely adopted in
smart buildings and enterprise-level energy management systems, it supports operational assessment and control.
Product Features
■The three-phase intelligent rail meter measures active and reactive power in both forward and reverse
directions. It simultaneously monitors A, B, and C phase voltages, currents, active/reactive power,
power factor, grid frequency, and total power consumption, with maximum demand recording
capability. The meter stores cumulative data for active/reactive power, forward/reverse total, peak,
valley, and flat periods, with the multi-rate billing function available only in high-capacity models.
■You can set two time zones and two schedules per year, eight daily periods and four rates:
peak, peak, flat and valley. The minimum interval between periods is 1 5 minutes.
■The system features data wheel display and data key display functions. Users can access voltage, current,
power factor, frequency, active power, reactive power, forward/reverse active energy, and forward/reverse
reactive energy through panel buttons. If no button is pressed within 8 seconds, the system automatically
switches to 4-second wheel display mode.
■Optional display of maximum demand for U, I, P, and Q, along with total peak, valley, flat, and off-peak power consumption for active and reactive power.
■Features active and reactive power pulse outputs for meter calibration and remote energy
collection. The passive opto-isolated output port delivers a pulse width of 80ms ± 20ms.
●The clock error is less than 0.5s per day, with automatic switching of calendar, timing, and leap year.
Technical Parameter
|
Project |
metric |
Project |
metric |
|
Accuracy class |
Active power: 0.5 level; reactive power: 2.0 level |
Operating temperature |
-10℃~+45℃ |
|
Rated voltage |
3×220/380V |
Relative humidity |
≤95% (no condensation) |
|
Working voltage |
0.9-1.1Un |
Power dissipation |
Voltage/current circuit <5VA4VA |
|
Current Specifications |
1. 5(6)A 5(60)A 20(80)A |
Clock error |
≤0.5s/d |
|
Reference frequency |
50Hz or 60Hz |
RS485 serial port |
MODBUS-RTU、 DT/T645-2007 protocol |
|
Starting current |
Direct / CT access: 0.004Ib/0.002Ib |
Traffic rate |
9600bps (default), 19200/ 4800/2400/1200bps optional |